THIS PRODUCT IS DISCONTINUED. The 4640 wall mount and 4645 panel mount Dissolved Oxygen Analyzers are
user-programmable analyzers designed for dissolved oxygen measurements in
a variety of applications from aeration control in sewage waste treatment
and effluent monitoring to measurement of dissolved oxygen in process liquors. |
![]() |
||
| FEATURES | BENEFITS | |
| Ultra-Reliable | No-maintenance oxygen sensor provides exceptional performance and reliability in the most demanding applications | |
| Comprehensive Diagnostics | Sensor checking insures measurement accuracy and alerts operator of abnormal conditions | |
| Microprocessor Flexibility | All functions are fully programmable to meet application requirements | |
| Compact Rugged Design | Available in surface NEMA 4X or 1/4 DIN panel mount versions. When installed, transmitter front is protected to NEIVIA 4X rating |
![]() |
![]() |
![]() |
|||
| Specisifcations | Floating Ball | Submersion | Rectractable Insertion |
||
| Sensor Type | D3010-166A sensor capsule | D3010-166A sensor capsule | D3010-166A sensor capsule | ||
| Response | Typically
20s for 90% of a step change of oxygen concentration at 68°F (20°C). |
Typically
20s for 90% of a step change of oxygen concentration at 68°F (20°C). |
Typically
20s for 90% of a step change of oxygen concentration at 68°F (20°C). |
||
| Temperature Compensation |
Automatic correction by means of an integral Pt 100 resistance thermometer. | Automatic correction by means of an integral Pt 100 resistance thermometer. | Automatic correction by means of an integral Pt 100 resistance thermometer. | ||
| Operating Temperature |
32 to 104°F (0 to 40°C) | 32 to 104°F (0 to 40°C) | 32 to 104°F (0 to 40°C) | ||
| Operating Pressure | Atmospheric | 60 PSI | 60 PSI | ||
| Minimum
liquid Velocity |
30 cm/s | 30 cm/s | 30 cm/s | ||
| Accuracy | ±0.1
ppm or ±1 % saturation within ±18°F (±10°C)
of the calibration temperature in the range 32° to 95°F (0 to 35°C) |
±0.1 ppm or ±1 % saturation within ±18°F (±10°C) of the calibration temperature in the range 32° to 95°F (0 to 35°C) | ±0.1 ppm or ±1 % saturation within ±18°F (±10°C) of the calibration temperature in the range 32° to 95°F (0 to 35°C) | ||
| Materials
of Construction |
Junction Box - diecast aluminum alloy. Support arm - ABS plastic Flotation collar polypropylene | Junction Box - diecast aluminum alloy. Support arm - ABS plastic | Stainless Steel/ CPVC | ||
| Junction
Box Environmental Protection |
NEMA 4X | NEMA 4X | Retractable probe supplied with 20' of direct interconnect cable | ||
| Mounting
and Process Connections |
Pipe mounting (1 1/2" OD) | Pipe mounting (1 1/2" OD) | 1 1/2"
NPT male retractable assembly Optional mounting T adapter 1 1/2" NPTF x 1/2" NPTF inlet and outlet |
||
| Connection Cable | Part #D1086-232. Maximum distance 3250 ft. (1000m) | Part #D1086-232. Maximum distance 3250 ft. (1000m) | Part #D1086-232. Maximum distance 3250 ft. (1000m) | ||
Support Arm |
ABS plastic OD 1 1/2". Schedule 40 for 10ft; schedule 80 for 10 to 20 ft. special | ABS plastic OD 1 1/2". Schedule 40 for 10ft; schedule 80 for 10 to 20 ft. special | ; Not applicable |
Display Information: |
Insulation: Retransmission |
|
|
||